The Faisalabad Electric Supply Company (FESCO) overcharged consumers by Rs. 1.26 billion during FY2024-25 by billing them for 30.81 million electricity units beyond the supply recorded at the relevant feeders, according to an audit report by the Auditor General of Pakistan.

The audit reviewed 1,394 FESCO feeders and found that 160 had negative unit balances. This means the electricity billed to consumers was higher than the units recorded as received by those feeders.

The reported discrepancies ranged from 0.1 percent to 187.6 percent, with the total financial impact calculated at Rs. 1,263.07 million.

The situation deteriorated compared with FY2023-24, when auditors found similar discrepancies across 125 of 1,369 feeders. Those feeders involved 16.58 million excess units, with an estimated impact of Rs. 497.40 million.

In FY2024-25, the number of affected feeders increased to 160, while the excess units rose to 30.81 million.

FESCO Offers Explanation for Extra Billing

The audit attributed the irregularities to poor monitoring of billing records and inadequate internal controls over electricity accounting.

According to auditors, the practice not only placed an additional burden on consumers but also inflated the company’s reported revenue and obscured actual distribution losses.

FESCO management told auditors that negative figures on certain 11-kilovolt feeders resulted from dual electricity supply arrangements for sensitive consumers. It also cited load transfers between feeders during technical faults.

The company further argued that consumers connected to the affected independent feeders had not lodged complaints about excessive billing.

Auditors did not accept these explanations. They maintained that dual supply arrangements and load transfers could not justify negative feeder balances without matching the electricity received against the units billed to consumers.

Audit Committee Demands Technical Records

The issue was taken up by the Departmental Accounts Committee (DAC) during its February 9-10, 2026 meeting.

The committee instructed FESCO to submit technical explanations and documentary evidence to support its position. This included electricity supply records at grid ends and corresponding consumer billing data.

The audit identified non-compliance with the WAPDA Commercial Procedures Manual as the basis of the irregularity.

It recommended that FESCO follow the committee’s instructions and provide the required supporting records to resolve the discrepancies.

The findings form part of the Auditor General’s review of FESCO’s financial and operational performance for FY2024-25.